Skip to main content Scroll Top
19th Ave New York, NY 95822, USA

ChlorGuard Control Panel

ChlorGuard Electro-Pneumatic Control Panel

For many years, the bespoke ChlorGuard™ control panel provides a robust philosophy for valve shutdown while also offering feedback signals so that the end user can monitor the status of the system. Process functionality has also been built in to assist the end user with activities such as closing the gas valves of an empty vessel before replacing.

Product Information Table
Dimensions H760mm x W415mm x D315mm
Construction Zintec steel welded construction. Separate pneumatic & electrical compartment. Hinged lockable outer cover c/w 3 mm perspex panel
Protection IP44
Finish 2 pack epoxy – RAL 1021
Power Supply 110/230Vac - 50/60Hz
Control ~ Pneumatic Manual, Automatic, Isolate via status control levers door mounted
Control ~ Electrical Signal from gas detectors. Manual from remote closure button. Key test switch
Visual Signal Alarm, mains power, stand by low battery, DC fuse, Pressure.
Signal Telemetry (Volt free contact) All NC or NO contacts available - Mains power failure, low pressure, low battery, alarm & levers not in open position.
Solenoid Valves 12Vdc for NC and 24Vdc for NO
Option 12V DC Power take off for strobe light to indicate:
a) Lever not in auto
b) Reset button not pressed to cancel alarm
Battery 12Vdc or 24Vdc – 7Ah

Design Features

Air Supply

  • Recommend stand alone air receiver/compressor is used dedicated to ChlorGuard
  • Sufficient Air for two closures
  • System designed and approved to Pressure Equiptment Directive 2014/68/EU Module-H

Control Panel

  • Standard panel uses Normally Closed Solenoid Vales (NC). This avoids plant shutdown when mains power fails and battery drains.
  • Fail-Safe panel uses Normally Open Solenoid Vales (NO) to avoid potential plant shutdown when mains power fails and battery drains.
  • One to four banks available for shutting down up to twenty cylinder valves or twelve drum valves
  • For use with nitrogen or compressed air
  • Battery back-up available for Standard and Fail-Safe
  • Solenoid valves are activated by gas detection alarm or remote stop signal to the electrical control panel
  • During closure compressed air supplied for up to 30 seconds
  • Key Test function available

CE Conformity with:

  • Machinery Directive (2006/42/EC)
  • Low Voltage Directive (2014/35/EU)
  • EMC Directive (2014/30/EU)