Skip to main content Scroll Top
19th Ave New York, NY 95822, USA

GassGuard Compressor/Receiver Assembly

GASSGUARD COMPRESSOR/RECEIVER ASSEMBLY

The GassGuard™ system is pneumatically operated and as such requires a bespoke compressor and receiver assembly to drive the system upon activation.  For redundancy, the receivers are sized with enough capacity for 2 enclosures should the compressor fail.  The compressors specified are very low maintenance, being oil free, and will provide many years of reliable operation.

Manufacturing Specification
Compressor Type Oil Free Piston Compressor
Capacity 130 – 190 L/min
Motor Size 1.1 - 1.5 kW
Motor Protection IP54
Power Supply 110/230Vac - 50/60Hz
Receiver Capacity 127, 230 and 270 litres
Receiver Size
  • D508mm x H1505mm
  • D508mm x H1825mm
  • D508mm x H1950mm
Fitted with
  • Gauge
  • Safety valve
  • Drain Valve (manual)
  • Pressure switch starter
Sound Level 71dB(A)

Manufacturing Specification

EC Conformity Procedure Pressure Equipment Directive 2014/68/EU Modules B & D
EC Type Examination Certificate No. CEN-006062/B1-02
Technical Standard Used BS.EN286-1: 1998 Class 2
Design Pressure 11.0 Barg
Design Temperature -10 to +85°C
Hydraulic Test Pressure 16.5 Barg
Vessel Design Life 20 Years - based on a fatigue criteria of the following pressure cycles: 1040 Cycles of Full Pressure Range (i.e. start up/shutdown cycles + 1752000 Cycles of range 2.0 Barg)
Finish Primed, blue gloss RAL 5015

Air Supply

  • Recommend stand alone air receiver/compressor is used dedicated to ChlorGuard
  • Sufficient Air for two closures
  • System designed and approved to Pressure Equipment Directive 2014/68/EU Module-H

CE Conformity with:

  • Pressure Equipment Directive 2014/68/EU